3 Error Tables
3-90
NJ-series Troubleshooting Manual (W503)
04BA0000 hex Connection
Error
between
Inverter and
Communica-
tions Unit
An error occurred in
the connection
between the
Inverter and the
EtherCAT Commu-
nications Unit for
the Inverter.
• Contact failure between the
Inverter and the EtherCAT
Communications Unit for the
Inverter.
• Inverter trip was reset.
• The Inverter was initialized or
the mode was changed.
• The EtherCAT Communications
Unit for the Inverter failed.
S MX2/RX
Series Inverter
EtherCAT
Communica-
tion Unit
User’s Manual
(Cat. No. I574)
04BB0000 hex Inverter
Warning
An Inverter warn-
ing was detected.
• An Inverter warning was
detected.
S Same as
above.
04BC0000 hex Inverter Trip An Inverter trip was
detected.
• An Inverter trip was detected. S Same as
above.
34F00000 hex PDO Setting
Error
There is an illegal
setting value in the
PDO mapping.
• The PDO mapping or Sync-
Manager settings are incorrect.
S Same as
above.
EtherCAT FQ-M-series Specialized Vision Sensors for Positioning
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info
78080000 hex TRIG Input
Error
A TRIG signal was
input when the
BUSY signal for
Sensor measure-
ment was ON.
• A TRIG signal was input when
the BUSY signal for Sensor
measurement was ON.
• Chattering occurred for a con-
tact input.
SFQ-M-series
Specialized
Vision Sensor
for Positioning
User’s Manual
(Cat. No.
Z314)
780A0000 hex Scene Data
Error
The scene data to
switch to is cor-
rupted.
• The power supply was inter-
rupted when the scene data to
switch to was saved.
S Same as
above.
780B0000 hex Model Error A model was re-
registered with an
image with low con-
trast.
• A model was re-registered with
an image with low contrast.
S Same as
above.
780C0000 hex Logging Error Some data was not
saved when logging
data to files on an
SD card.
• Too much data to log in files
occurred in a short period of
time, and writing to the SD card
could not keep up.
S Same as
above.
780D0000 hex Output Time-
out
A timeout occurred
in data output hand-
shaking control for
measurement
results.
• The data output handshaking
controls in the program (i.e., the
ON/OFF timing of the DSA sig-
nal) are not correct.
• The output control timeout time
is too short in comparison with
the program processing time.
S Same as
above.
780E0000 hex Output Size
Error
The data output
size setting and the
PDO mapping set-
ting do not agree.
• The EtherCAT data output size
setting in the Sensor and the
PDO mapping setting in the
EtherCAT master do not agree.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info