4 Installation and Wiring
4-32
NJ-series CPU Unit Hardware User’s Manual (W500)
Precautions for Safe Use
Use crimp terminals for wiring.
Do not connect bare stranded wires directly to terminals.
Tighten the terminal block screws to the torque of 0.5 N·m.
Use crimp terminals (M3) having the dimensions shown below.
Wiring
Make sure that all Units are connected properly.
Do not allow wire clippings, shavings, or other foreign material to enter any Unit during wiring.
To allow heat to dissipate, always remove any dustproof labels that are on the top of the Units
before you turn ON the power supply.
Wire the Units so that they can be easily replaced.
Make sure that the I/O indicators are not covered by the wiring.
Do not place the wiring for I/O Units in the same duct or raceway as power lines. Inductive noise
can cause errors in operation.
Tighten the terminal screws to the torque of 0.5 N·m.
6.2 mm max.
6.2 mm max.
OD211
0 123
4
5 6 7
8 9 10 11 12 13 14 15
OD211
01234567
8 9 10 11 12 13 14 15
After wiringDuring wiring
Remove the label.
17.5 mm
Screw (M3 screw with
self-raising pressure plate)