EasyManua.ls Logo

Omron NJ301-1100 - Page 170

Omron NJ301-1100
400 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Installation and Wiring
4-50
NJ-series CPU Unit Hardware User’s Manual (W500)
Forced Air Circulation (by Fan in Closed Panel)
Room Cooling (Cooling the Entire Room Where the Control Panel Is Located)
The Controller may not start normally if the temperature is below 0C when the power is turned ON.
Maintain an air temperature of at least approximately 5C inside the panel, by implementing measures
such as installing a low-capacity space heater in the panel. Alternatively, leave the Controller power ON
to keep the Controller warm.
Low Temperatures
Fan
Controller
Controller
Forced Air Circulation
Room Cooling
Cooler
Control panel

Table of Contents

Other manuals for Omron NJ301-1100

Related product manuals