3-15
3 Configuration Units
NJ-series CPU Unit Hardware User’s Manual (W500)
3-3 Power Supply Units
3
3-3-1 Models and Specifications
*1 The AC and DC values above are given for a cold start, and the AC values are at room temperature. The AC inrush con-
trol circuit uses a thermistor element with a low-temperature current control characteristic. If the ambient temperature is
high or the Controller is hot-started, the thermistor will not be sufficiently cool, and the inrush current given in the table
may be exceeded by up to twice the given value. The DC inrush control circuit uses a capacitor-charging delay circuit. If
the power is OFF for only a short time for a hot-start, the capacitor will not sufficiently discharge and the inrush current
given in the table may be exceeded by up to twice the given value. An inrush current of approximately 4 A may occur and
continue for 1 s when the power is turned ON. When selecting fuses, breakers, and external DC power supply devices for
external circuits, allow sufficient margin in shut-off performance.
*2 Internal components in the Power Supply Unit will deteriorate or be damaged if the Power Supply Unit is used for an
extended period of time exceeding the power supply output capacity or if the outputs are shorted.
*3 Supported only when mounted to CPU Rack.
*4 The tests can also be performed with the LG terminal and GR terminal connected to each other.
*5 Change the applied voltage gradually using the adjuster on the Tester. If the full dielectric strength voltage is applied or
turned OFF using the switch on the Tester, the generated impulse voltage may damage the Power Supply Unit.
Shock resistance
147 m/s
2
3 times each in X, Y, and Z directions (Relay Output Unit: 100 m/s
2
) (according to IEC
60068-2-27)
Ambient operating
temperature
0 to 55C
Ambient operating
humidity
10% to 90% (with no condensation)
Atmosphere Must be free from corrosive gases.
Ambient storage tem-
perature
20 to 75C
Item Specifications