EasyManua.ls Logo

Omron NJ301-1200 - Page 152

Omron NJ301-1200
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Error Tables
3-90
NJ-series Troubleshooting Manual (W503)
04BA0000 hex Connection
Error
between
Inverter and
Communica-
tions Unit
An error occurred in
the connection
between the
Inverter and the
EtherCAT Commu-
nications Unit for
the Inverter.
Contact failure between the
Inverter and the EtherCAT
Communications Unit for the
Inverter.
Inverter trip was reset.
The Inverter was initialized or
the mode was changed.
The EtherCAT Communications
Unit for the Inverter failed.
S MX2/RX
Series Inverter
EtherCAT
Communica-
tion Unit
User’s Manual
(Cat. No. I574)
04BB0000 hex Inverter
Warning
An Inverter warn-
ing was detected.
An Inverter warning was
detected.
S Same as
above.
04BC0000 hex Inverter Trip An Inverter trip was
detected.
An Inverter trip was detected. S Same as
above.
34F00000 hex PDO Setting
Error
There is an illegal
setting value in the
PDO mapping.
The PDO mapping or Sync-
Manager settings are incorrect.
S Same as
above.
EtherCAT FQ-M-series Specialized Vision Sensors for Positioning
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info
78080000 hex TRIG Input
Error
A TRIG signal was
input when the
BUSY signal for
Sensor measure-
ment was ON.
A TRIG signal was input when
the BUSY signal for Sensor
measurement was ON.
Chattering occurred for a con-
tact input.
SFQ-M-series
Specialized
Vision Sensor
for Positioning
User’s Manual
(Cat. No.
Z314)
780A0000 hex Scene Data
Error
The scene data to
switch to is cor-
rupted.
The power supply was inter-
rupted when the scene data to
switch to was saved.
S Same as
above.
780B0000 hex Model Error A model was re-
registered with an
image with low con-
trast.
A model was re-registered with
an image with low contrast.
S Same as
above.
780C0000 hex Logging Error Some data was not
saved when logging
data to files on an
SD card.
Too much data to log in files
occurred in a short period of
time, and writing to the SD card
could not keep up.
S Same as
above.
780D0000 hex Output Time-
out
A timeout occurred
in data output hand-
shaking control for
measurement
results.
The data output handshaking
controls in the program (i.e., the
ON/OFF timing of the DSA sig-
nal) are not correct.
The output control timeout time
is too short in comparison with
the program processing time.
S Same as
above.
780E0000 hex Output Size
Error
The data output
size setting and the
PDO mapping set-
ting do not agree.
The EtherCAT data output size
setting in the Sensor and the
PDO mapping setting in the
EtherCAT master do not agree.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info