EasyManua.ls Logo

Omron NJ301-1200 - Page 75

Omron NJ301-1200
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-13
3 Error Tables
NJ-series Troubleshooting Manual (W503)
3-1 Errors by Source
3
3-1-2 Errors in the PLC Function Module
Errors Related to FINS Communications
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info
14010000 hex CPU Bus
Unit Setup
Area Error
An error was
detected in the
memory check of
the Setup Area for
CPU Bus Units.
The power supply to the Con-
troller was interrupted or com-
munications with the Sysmac
Studio were disconnected while
downloading the CPU Bus Unit
Settings.
S NJ-series
CPU Unit Soft-
ware User’s
Manual (Cat.
No. W501)
34100000 hex IP Address
Table Setting
Error
The IP address
table settings are
incorrect.
The IP address conversion
method is set to the combined
method or the IP address table
method, but the IP address
table settings are incorrect.
S Same as
above.
34130000 hex FINS/TCP
Connection
Table Setting
Error
The FINS/TCP con-
nection table is
incorrect.
The power supply to the Con-
troller was interrupted or com-
munications with the Sysmac
Studio were disconnected while
downloading the FINS/TCP
connection table.
S Same as
above.
34110000 hex Unknown
Destination
Node
The send destina-
tion node is not
known.
The send destination node was
not found when a FINS mes-
sage was sent.
S Same as
above.
80100000 hex Packet Dis-
carded
One or more pack-
ets were discarded.
A FINS response addressed to
the CPU Unit was received.
The send designation Unit for
the FINS response does not
exist.
S Same as
above.
80110000 hex Packet Dis-
carded
One or more pack-
ets were discarded.
An attempt was made to send a
FINS response with over 2002
bytes.
An attempt was made to route a
FINS response with over 2002
bytes.
Packet was received with a No
Such Unit routing error.
Packet was received with a
Routing Error routing error.
Packet was received with a No
Routing Table routing error.
Packet was received with an
Event Area Size Over Limit
routing error.
There is insufficient space in
the internal buffer.
FINS message routing failed
because the communications
load is too high.
S Same as
above.

Table of Contents