Communications Setup
The following table shows the communications settings required at the NS-V1/V2 PT and the
host to connect to the host by means of Host Link communications.
Setup
location
Settings (See note 2.)
NS-V1/V2 PT Baud rate: 9,600 or 19,200 bps (See note 1.)
Host Start bits: 1 bit
Data: 7 bits
Stop bits: 2 bits
Parity: Even
Host Link unit number: 0
Baud rate: 9,600 or 19,200 bps (See note 1.)
Note 1: The baud rate settings must be the same for both the NS-V1/V2 PT and the host.
2: Use the 1:N protocol setting.
1-2-2 Applicable PLCs
The OMRON PLCs listed below can be connected as hosts using Host Link communications.
The connection can be made either directly to the built-in serial port on the CPU Unit or to a
Host Link Unit mounted to the PLC.
C Series
C200HS, C200HX/HG/HE(-Z), CQM1, CQM1H, CPM2A/CPM2C, CPM1/CPM1A, C500,
C1000H, C2000H
CV Series
CV500, CV1000, CV2000, CVM1
CS/CJ Series
CS1G/CS1H, CS1G-H/CS1H-H, CJ1G, CJ1G-H/CJ1H-H, CJ1M, CP1H/CP1L, CJ2H,
CJ2M