Appendices
A - 98
NX-series Digital I/O Unit User’s Manual (W521)
*1. The default value and data range for Number of Entries are as follows.
*2. The detailed data and meaning of the set values for Load Rejection Output for Output Bit (32 bits) are as follows.
Bit 0: Load Rejection Output for Output Bit 00
Bit 1: Load Rejection Output for Output Bit 01
·
·
·
Bit 31: Load Rejection Output for Output Bit 31
Index
(hex)
Subindex
(hex)
Object name
Default
value
Data range Unit
Data
type
Acc
ess
I/O
allo-
cat-
ion
Data
attri-
bute
5013  Load Rejection DWord
Setting
 
00 Number of Entries
*1 *1
 USINT RO Not
possi
ble

01 Load Rejection Output for
Output Bit (32 bits)
00000000
hex
00000000 to
FFFFFFFF hex
*2
 DWORD RW Not
possi
ble
Y
NX Units Default value Data range
NX-OD6121-5/OD6256-5 1 1 (fixed)
Other models 0 0 (fixed)
Set value Meaning
0OFF
1 Hold the present value.