7 Troubleshooting
7-8
NJ/NX-series Database Connection CPU Units User’s Manual (W527)
Errors Related to DB Connection Service
Event code Event name Meaning Assumed cause
14D00000hex Spool Memory
Corrupted
The Spool
memory is
ï‚– The user application made an
invalid writing to the Spool
S
7-16
14D20000hex Execution Log
Save Failed
Failed to save
the Execution
Log to the SD
Memory Card.
ï‚– An SD Memory Card is not
inserted.
ï‚– The SD Memory Card is not the
correct type of card.
ï‚– The format of the SD Memory
Card is not correct.
ï‚– The SD Memory Card is
write-protected.
ï‚– The capacity of the SD Memory
Card is insufficient.
ï‚– The SD Memory Card is
S U
7-17
14D30000hex SQL
Execution
Failure Log
Save Failed
Failed to save
the SQL
Execution
Failure Log to
the SD Memory
Card.
ï‚– An SD Memory Card is not
inserted.
ï‚– The SD Memory Card is not the
correct type of card.
ï‚– The format of the SD Memory
Card is not correct.
ï‚– The SD Memory Card is
write-protected.
ï‚– The capacity of the SD Memory
Card is insufficient.
ï‚– The SD Memory Card is
S U
7-18
35300000hex DB
Connection
Setting Error
The DB
Connection
settings are not
correct.
ï‚– The power supply to the
Controller was interrupted
during a download of the DB
Connection settings.
ï‚– The DB Connection settings are
not correct because the power
supply to the Controller was
interrupted during a Clear All
Memory operation.
ï‚– The DB Connection settings are
not correct because the power
supply to the Controller was
interrupted during a Restore
operation.
ï‚–
Non-volatile memory failed.
S
7-19
85100000hex DB
Connection
Disconnected
Error
The DB
Connection was
disconnected
due to an error.
ï‚– The power supply to the server
is OFF.
ï‚– The DB is stopped in the
server.
ï‚– The Ethernet cable connector is
disconnected.
ï‚– The Ethernet cable is broken.
ï‚–