BN50S / BN75S / BN100S / BN150S / BN220S / BN300S
4
37
The UPS operation mode can be set if the power switch is turned ON while the beeper stop /test
switch is pressed.
Note: While in setting mode, output from the power supply output is OFF even if the power
switch is ON.
(1) When the beeper stop/test switch is briefl y pressed (for less than 1 second), the next item is
displayed.
Cold start ON/OFF setting
Output voltage setting
Input power sensitivity setting
Power supply output stop delay time setting
Signal input/output test
(2) The unit enters the “individual item setting mode” when the beeper stop/test switch is
pressed and held (for more than 1 second).
(3) When the power switch is turned OFF, the setting mode quits and the unit enters power
switch OFF status (status
).
2-2 Settings