35
4
BU1002SWG / BU3002SWG
Setting for whether or not to perform battery test (setting switch
3
)
Factory setting: OFF
1 2 53 4 86 7
ON DIP
OFF: The battery test is automatically executed once every 4 weeks.
ON: Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
Auto startup mode setting (setting switch
4
)
Factory setting: OFF
OFF: (Mode A) After UPS stopped, the UPS is automatically started immediately when “ON” is
detected for the AC input.
ON:(ModeB) After UPSstopped, the UPSis automatically startedin theAC input’s “OFFto ON”
timing that is detected.
(DenitionofACinputOFF:WhenACinputisOFFfor1secondormore)
* Setting switch
4
is valid when the auto startup after recovery from power failure setting (setting switch
2
) is set to OFF (auto restart is performed).
* This setting mode is valid only after the UPS has been stopped by the contact signal backup stop
signal (BS).
* When a cable is connected to the RS-232C connector and the UPS monitoring software is used, the
unit operates in Mode A regardless of this setting.