Safety precautions
vi
Caution
(for use)
Never touch the metal part of the input plug if it is disconnected while
the unit is operating.
Doing so may result in electric shock.
The leak current of this product itself is less than the value of the safety standard (leak
current: 1 mA). However, because connected equipment causes the leak current to
increase, you must never touch the metal part of the input plug.
When the unit is operating, voltage is generated in the metal parts of the input plug via
capacitors in the internal circuit, regardless of the elapsed time.
Do not allow the unit to come in contact with water.
Doingsomaycauseanelectricshockorare.
If the unit becomes wet, stop using it and have it inspected and/or repaired.
For repair, contact Omron representatives.
When the battery is dead, replace it immediately or stop using the unit.
Continuing the use of it may cause a re.
Using a dry cloth, periodically wipe the dust from the AC input plug,
power supply output receptacles and output terminal block.
Accumulateddustmaycauseare.
Do not use the unit in a closed place and do not cover the unit.
Doingsomaycauseabnormalheatingorare.
If you notice abnormal sound or smell, smoke, or leakage from the
inside, immediately turn off the power switch and disconnect the AC
input plug from a wall outlet (commercial power).
Usingtheunitundersuchconditionsmaycauseare.
If you notice such a condition, stop using the unit and contact Omron representatives for inspec-
tion and repairs.
Use the unit under the conditions in which you can immediately disconnect the AC input
plug from a wall outlet (commercial power) in the case of an abnormal event.
If uid leaks from the unit, do not touch the uid.
Doing so may cause blindness or burns.
If the uid contactsyoureyes or skin, wash it out withlotsof clean water and consult your
doctor.
Do not place objects heavier than 25kg on the unit, and do not drop
heavy objects onto the unit.
Doing so may cause distortion/damage to the case or a failure of the internal circuit, which
maycauseare.
* The values in the table are the expected life under standard
use conditions and are not guaranteed.
Ambient temperature
20°C
30°C
Expected life
4 to 5 years
2 to 2.5 years