Mechanical Installation
2
2.3 Installation Position and Distance
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 33
A - 50 mm (2 in.) minimum
B - 30 mm (1.2 in.) minimum on both
sides
C - 2 mm (0.08 in.) minimum between
each drive
D - 120 mm (4.7 in.) minimum above
and below
Figure 2.3 Installation Distances for Multiple Drives (Side-by-Side)
Note:
Align the tops of drives that have different dimensions to help when replacing cooling fans.
Remove the top protective covers of all drives when mounting UL Type 1 enclosure drives side-by-side.
Figure 2.4 Enclosed Wall-Mounted Type (UL Type 1) Installed Side-by-Side