2.8 Change the Drive Enclosure Type
52 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
A - Hooks
B - Rear side of top protective cover
C - Temporary placement holes
Figure 2.49 Attach the Top Protective Cover
Attach the Conduit Bracket
1. Align the screw holes on the stay bracket with the screw holes on the base. Tighten the included screws to
a tightening torque of 0.98 Nm to 1.33 Nm (8.67 lb.in. to 11.77 lb.in.) to attach the stay bracket to the
base.
A - Stay bracket
B - Base
C - Screw
Figure 2.50 Assemble Conduit Bracket 1
2. Align the screw holes on conduit bracket 1 with the screw holes on the drive and push the bracket into
position. Use the screws to attach the bracket.
Tighten the screws to a correct tightening torque.
Screw A: 3.92 Nm to 4.90 Nm (34.70 lb.in. to 43.37 lb.in.)
Screw B: 8.83 Nm to 10.79 Nm (78.15 lb.in. to 95.49 lb.in.)