Parameter Details
12
12.7 H: TERMINALS
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 729
H5-17 ENTER@CPU Busy Response
No.
(Hex.)
Name Description
Default
(Range)
H5-17
(11A1)
Expert
ENTER@CPU Busy
Response
Sets operation when the EEPROM write command is sent without EEPROM write available.
Usually it is not necessary to change this setting.
1
(1, 2)
1 : Ignore (No Write)
2 : Write RAM Only
H5-18 Mbus Speed Filter over Comms
No.
(Hex.)
Name Description
Default
(Range)
H5-18
(11A2)
Mbus Speed Filter over
Comms
Sets the filter time constant used when monitoring motor speed during Modbus communications
or with a communication option.
0 ms
(0 - 100 ms)
Sets the filter time constant when you monitor the output frequency or motor speed during Modbus
communications or use of the communication option.
These are the Modbus registers:
003EH (Output Frequency)
003FH (Output Frequency)
0044H (U1-05: Motor Speed)
00ACH (U1-05: Motor Speed)
00ADH (U1-05: Motor Speed)
H5-20 Mbus Par Reload Mode
No.
(Hex.)
Name Description
Default
(Range)
H5-20
(0B57)
Mbus Par Reload Mode
Sets the function to immediately enable updated Modbus communications parameters.
1
(1, 2)
1 : Reload@Power Cycle
2 : Reload Now
Note:
The setting value automatically returns to H5-20 = 1 after you enable Modbus communications parameter changes.
The setting values of these parameters are enabled:
H5-01 [Mbus Address]
H5-02 [Mbus BaudRate]
H5-03 [Mbus Parity]
H5-06 [Mbus Tx Wait Time]
H5-25 Mbus 5A Reg1 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-25
(1589)
RUN
Mbus 5A Reg1 Selection
Returns the contents of the specified Modbus communications register when responding to the
master device.
0044H (U1-05)
(0000H - FFFFH)
H5-26 Mbus 5A Reg2 Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-26
(158A)
RUN
Mbus 5A Reg2 Selection
Returns the contents of the specified Modbus communications register when responding to the
master device.
0045H (U1-06)
(0000H - FFFFH)

Table of Contents

Other manuals for Omron Q2A-A4018-AAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A-A4018-AAA and is the answer not in the manual?

Omron Q2A-A4018-AAA Specifications

General IconGeneral
BrandOmron
ModelQ2A-A4018-AAA
CategoryController
LanguageEnglish

Related product manuals