7.4 Faults
272 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
Code Name Causes Possible Solutions
Uv3 Soft Charge Answerback Fault
The relay or contactor on the soft-charge bypass
relay is damaged.
Re-energize the drive.
If the fault stays, replace the control board or the drive.
Check monitor U4-06 [SoftChgRelay Maint] shows the
performance life of the soft-charge bypass relay. If U4-06 is
more than 90%, replace the board or the drive. For information
about replacing the board, contact the manufacturer or your
nearest sales representative.
Note:
Do a Fault Reset to clear the fault.
Fault trace is not available for this fault.