Parameter List
11
11.7 F: OPTIONS
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 429
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F7-64
(0784)
PZD5 Write
Sets the Modbus address for PZD5 (PPO output). A value of 0, 1, or 2 will disable the
PZD5 (PPO output) write operation to the Modbus register.
0 663
F7-65
(0785)
PZD6 Write
Sets the Modbus address for PZD6 (PPO output). A value of 0, 1, or 2 will disable the
PZD6 (PPO output) write operation to the Modbus register.
0 663
F7-66
(0786)
PZD7 Write
Sets the Modbus address for PZD7 (PPO output). A value of 0, 1, or 2 will disable the
PZD7 (PPO output) write operation to the Modbus register.
0 663
F7-67
(0787)
PZD8 Write
Sets the Modbus address for PZD8 (PPO output). A value of 0, 1, or 2 will disable the
PZD8 (PPO output) write operation to the Modbus register.
0 663
F7-68
(0788)
PZD9 Write
Sets the Modbus address for PZD9 (PPO output). A value of 0, 1, or 2 will disable the
PZD9 (PPO output) write operation to the Modbus register.
0 663
F7-69
(0789)
PZD10 Write
Sets the Modbus address for PZD10 (PPO output). A value of 0, 1, or 2 will disable the
PZD10 (PPO output) write operation to the Modbus register.
0 663
F7-70
(078A)
PZD1 RD (StatWord)
Sets the Modbus address for PZD1 (PPO Read). PZD1 (PPO input) functions as the
ZSW when F7-70 = 0.
0 663
F7-71
(078B)
PZD2 RD (OutFreq)
Sets the Modbus address for PZD2 (PPO Read). PZD2 (PPO input) functions as the
HIW when F7-71 = 0.
0 664
F7-72
(078C)
PZD3 Read
Sets the Modbus address for PZD3 (PPO Read). A value of 0 will disable the PZD3
(PPO input) load operation from the Modbus register.
0 664
F7-73
(078D)
PZD4 Read
Sets the Modbus address for PZD4 (PPO Read). A value of 0 will disable the PZD4
(PPO input) load operation from the Modbus register.
0 664
F7-74
(078E)
PZD5 Read
Sets the Modbus address for PZD5 (PPO Read). A value of 0 will disable the PZD5
(PPO input) load operation from the Modbus register.
0 664
F7-75
(078F)
PZD6 Read
Sets the Modbus address for PZD6 (PPO Read). A value of 0 will disable the PZD6
(PPO input) load operation from the Modbus register.
0 664
F7-76
(0790)
PZD7 Read
Sets the Modbus address for PZD7 (PPO Read). A value of 0 will disable the PZD7
(PPO input) load operation from the Modbus register.
0 664
F7-77
(0791)
PZD8 Read
Sets the Modbus address for PZD8 (PPO Read). A value of 0 will disable the PZD8
(PPO input) load operation from the Modbus register.
0 664
F7-78
(0792)
PZD9 Read
Sets the Modbus address for PZD9 (PPO Read). A value of 0 will disable the PZD9
(PPO input) load operation from the Modbus register.
0 664
F7-79
(0793)
PZD10 Read
Sets the Modbus address for PZD10 (PPO Read). A value of 0 will disable the PZD10
(PPO input) load operation from the Modbus register.
0 665