Q2A 19
D1000 kit - DC Supply with Regenerative Active Front End system
Regenerative DC bus supply unit (D1000)
EMC filter
Low harmonic filter
Reference: CIMR-DC@
4A0005 4A0010 4A0020 4A0030 4A0040 4A0060 4A0100 4A0130 4A0185 4A0270 4A0370
Max. applicable motor capacity (kW) 3.7 7.5 15 22 30 45 75 110 160 220 315
Rated output capacity (kW)
*1
*1. Rated output capacity is calculated with a rated input voltage of 400 V.
5 10 20 30 40 60 100 130 185 270 370
Rated input current AC (A) 8 16 30 43 58 86 145 210 300 410 560
Rated output current DC (A) 8 15 30 45 61 91 152 197 280 409 561
Rated input voltage 3-phase 380 to 480 VAC
Rated output voltage 660 VDC
Rated frequency 50/60 Hz
Input power factor > 0.99
Carrier frequency 6 4 2
Degree of protection IP20 IP00
Ambient humidity 95% RH or less (without condensation)
Storage temperature -20 to 60ºC
Ambient temperature -10 to 50ºC
Reference: B84143@
A0020R106 A0035R106 A0065R106 B0180S080 B0400S080 B1000S080
Rated current (A) 20 35 65 180 400 1000
Leakage current (mA) 3.1 3.4 3.4 < 21 < 21 < 40
Rated voltage 300/520 VAC
Rated frequency 50/60 Hz
Rated temperature 50ºC
Degree of protection IP20
Reference: B84143G@
0008R176 0016R176 0030R176 0043R176 0058R176 0086R176 0145R176 0210S176 0300S176 0410S176 0560S176
Rated current (A) 8 16 30 43 58 86 145 210 300 410 560
Heat loss (W)
*1
*1. Heat loss at nominal current and 20ºC winding temperature with harmonics.
75 140 165 240 260 300 515 665 855 1398 1970
Rated voltage 305/530 VAC
Rated frequency 50/60 Hz
Rated temperature 50ºC
Degree of protection IP00
D1000 kit
Motor
Power
supply
Q2A
Regenerative DC
bus supply unit
(D1000)
123 n
1
~
n
EMC filter
Low harmonic
filter
I175E-EN-01+Q2A+Datasheet.fm Seite 19 Montag, 26. März 2018 3:18 15