11-11
11-4 Troubleshooting
OMNUC G5-SERIES AC SERVOMOTOR AND SERVO DRIVE USER'S MANUAL
  11
Troubleshooting and Maintenance
12 0 Overvoltage
The power supply voltage exceeded 
the allowable input voltage range, 
causing the voltage between the 
positive and negative terminals in the 
converter to exceed the specified 
value. The power supply voltage is 
high. The voltage was suddenly 
increased by the phase advance 
capacitor or the uninterruptible power 
supply (UPS).
100-V models: Approx. 200 VDC 
(approx. 140 VAC)
200-V models: Approx. 400 VDC 
(approx. 280 VAC)
400-V models: Approx. 800 VDC 
(approx. 560 VAC)
· The regeneration resistor wiring is 
broken.
· The External Regeneration 
Resistor is inappropriate and 
cannot absorb all of the 
regenerative energy. The load 
inertia is too large, gravitational 
torque on the vertical axis is too 
large, or there is some other 
problem in absorbing the 
regenerative energy.
· The Servo Drive has failed (circuit 
failure).
Measure the voltage between the L1, 
L2, and L3 lines on the connector and 
the terminal block. Input the correct 
voltage. Remove the phase advance 
capacitor.
· Use a tester to measure the 
resistance of the external resistor 
between the B1 and B2 terminals 
on the Servo Drive. If the 
resistance is infinite, the wiring is 
broken. Replace the External 
Regeneration Resistor.
· Change the regeneration 
resistance and wattage to the 
specified values. (Calculate the 
regenerative energy and connect 
an External Regeneration 
Resistor with the required 
regeneration absorption capacity. 
Reduce the descent speed.)
· Replace the Servo Drive.
Alarm 
number
Name Cause Measures
Main Sub