S82J
S82J
5
Specifications
Ratings/Characteristics
Item
100
V
AC input/200 V
AC input
100 or 200 V
AC
(selectable)
100 to 240 V
AC input
100 or 200
VAC
(selected
automatic
ally)
10 W 25 W 50 W
(5, 12 V)
100 W (5,
12, 15 V)
300 W 600 W
50 W
(24 V)
100 W
(24 V)
150 W
Ef
ficiency (typical)
67% min. 76% min. 82% min. 77% min. 83% min. 82% min.
Input Voltage
100 V
AC
input
100 V
AC (85 to 132 V
AC), 1
10 to 170 VDC
(see note 1)
100 (85 to 132) or 200
(170 to 253) V
AC
(selectable)
100 to 240 V
AC (85 to
264 V
AC)
100 (85 to
132) or 200
(170 to
200 V
AC
input
200 V
AC (170 to 264 V
AC)
264) V
AC
(selected
automatical
ly)
Frequency
50/60 Hz (47 to 450 Hz)
Current
(see note
100 V
AC
input
0.35 A
max.
0.8 A
max.
1.4 A
max.
2.5 A
8 A max.
14 A max.
1.4 A
max.
2.5 A
max.
3.5 A max.
2)
200 V
AC
input
0.3 A
max.
0.6 A
max.
0.8 A
max.
1.4 A
4 A max. 7 A max.
0.8 A
max.
1.5 A
max.
2.1 A max.
Leakage
current
100 V
AC
input
0.5 mA max.
(see note
2)
200 V
AC
input
1 mA max.
Inrush
current
25°C,
100 V
AC
input
25 A max. 30 A max. 25 A max.
,
cold start)
(see note
2)
200 V
AC
input
50 A max. 60 A max. 50 A max.
Noise filter
Yes
Output
(see note
V
oltage adjustment
range
±
10% (adjustable with variable resistor (V
.ADJ))
3)
Ripple (see note 2)
2% (p-p) max.
Input
variation
100 V
AC
input
0.4% max. (at 85 to 132 V
AC input, 100% load)
0.4% max.
influence
200 V
AC
input
0.4% max. (at 170 to 264 VAC input, 100% load)
Load variation
influence
0.8% max. (with rated input, 10% to 100% load)
T
emperature variation
influence
0.05%/°
C max. (with rated input and output)
Rise time
200 ms max. (up to 90% of output voltage at
rated input and output)
300 ms max. (up to
90% of output voltage
at rated input and
output)
500 ms min. (up to 90% of output
voltage at rated input and output)
Hold time (see note 2) 20 ms min.
Additional
function
Overload protection
105% min. of rated load current, inverted L drop type, automatic reset (For
the 600-W model, the circuit will be shut OFF when the overload exceeds
5±
3s. Protection-ON alarm indicator lit. (see note 4)).
105 to 160% of rated
load current, inverted L
drop/Intermittent
operation type,
automatic reset)
105% min.
of rated
load
current,
inverted L
drop type,
automatic
reset
Overvoltage protection
(see note 5)
No Y
es (5-V
output
models
only)
Y
es, protection-ON
alarm indicator lit.
No Yes No
Overheat protection
No Yes,
protection
-ON
alarm
indicator
lit (see
note 4)
No
Protection-On alarm
indicator
No Y
es (color
, red)
No
Parallel operation
No Y
es, 5 units max.
No
Series operation
No Yes