S82J
S82J
6
Item
100 or 200
VAC
(selected
automatic
ally)
100 to 240 V
AC input
100 or 200 V
AC
(selectable)
100 V
AC input/200 V
AC input
Item
150 W100 W
(24 V)
50 W
(24 V)
600 W300 W100 W (5,
12, 15 V)
50 W
(5, 12 V)
25 W10 W
Other
Ambient temperature
Operating: See the derating curve in the Engineering Data section.
Storage: –25
°
C to 65
°
C (with no condensation and icing)
Ambient humidity Operating: 25% to 85%
Storage: 25% to 90%
Dielectric strength
3.0 kV
AC, 50/60 Hz for 1 min (between all inputs and all outputs)
Dielectric
strength
2.2 kV
AC, 50/60 Hz for 1 min (between all inputs
and all inputs/GR terminals)
2.2 kV
AC, 50/60 Hz for 1 min (between all inputs and GR
terminals)
---
1.0 kV
AC, 50/60 Hz for 1 min (between all outputs and GR
terminal)
Insulation resistance
100 M
min. (between all outputs and all inputs/GR terminals at 500 VDC)
V
ibration resistance
10 to 55 Hz, 0.375-mm double amplitude for 2 h each in X, Y
, and Z directions
Shock resistance
294 m/s
2
, 3 times each in
±
X,
±Y
, and
±
Z directions
T
erminal screw
tightening torque
0.74 N
S
m
1.08 N
S
m
0.74 N
S
m
1.08 N
S
m
Output indicator
Y
es (green)
Electromagnetic
interference (see note
2)
Conforms to FCC Class A
EMC
Emission Enclosure:
EN5501
1 class A
Emission AC Mains:
EN5501
1 class A
Immunity ESD:
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: ENV50140:
10 V/m
2
(80 MHz to 1 GHz) (level 3)
Immunity Conducted Disturbance:
ENV50141: 10 V (0.5 to 80 MHz) (level 3)
Immunity Burst:
EN61000-4-4:
2 kV power-line (level 3)
2 kV output line (level 4)
EMC standards
Conforms to EN50081-2 and EN50082-2
Conforms to
EN50081-2 and
EN50082-2 (see note
6)
With noise filter
,
confirms to EN50081-1
(see note 6 and 7)
Conforms to EN50081-2 and
EN50082-2
Approved
standards
UL UL508/1012 UL508 UL508/1012
Class 2
(per
UL1310),
UL508
(Listing)/
1950
UL508 (Listing)/
1012/1950
(see note 8)
CSA
CSA C22.2 No. 14
CSA EB1402C
Class 2
(per CSA
C22.2 No.
950),
CSA
C22.2 No.
14/
No. 950
CSA C22.2 No. 14/No.
950
VDE
EN50178 (VDE0160) and EN60950 EN50178 (VDE0160) and EN60950
For covered types, conforms to VDE
0106/P100
Weight
250 g
max. (see
note 9)
350 g
max. (see
note 9)
400 g
max. (see
note 9)
1,000 g
max.
2,000 g
max.
2,500 g
max.
500 g
max.
600 g
max.
1,000 g
max.
Note: 1. DC
inputs not included in safety standard approvals.
2.
At 100% load for rated input voltage (100 V
AC or 200 V
AC).
3.
The output specification is defined at the power supply output terminals.
4.
For resetting, turn OFF the power supply
, leave for more than three minutes, and then turn ON the power supply
.
5. For
resetting, turn OFF the power supply
, leave for more than one minutes (90 seconds min. for the 300-W models and 3 minutes
min.
for the 600-W models), and then turn ON the power supply
.
6. T
o ensure the Emission Enclosure rating ferrite ring cores (recommended model: S82Y-JC-T) should be used on all cabling.
7. To
ensure the Emission AC Mains rating for EN50081-1 (only for 200-V
AC input), a nose filter (recommended models: S82Y
-JF3-N
for
300-W
, S82Y
-JF6-N for 600-W) should be used on the input lines.
8.
With UL508, 150-W connector type has “Recognized” approval.
9.
The weight indicated is the weight of the open-frame type.