7. Pre-Operation Checklists / Maintenance Checklists
After wiring, mounting and beam alignment are done, check the operation of the F3SJ-B-02TS.
Pre-Operation Checklists
After installation, the highest level administrator must use the following checklist to verify the operation, plac-
ing a check mark in each of the boxes.
Checklists
- Installation Condition Check
The machine itself does not prevent the operation of safety functions such as stopping.
The hazardous part of a machine cannot be reached without passing through the detection zone of the
F3SJ-B-02TS.
The system is configured so that the F3SJ-B-02TS can always detect a worker who is working in the haz-
ardous zone.
The interlock reset switch is installed in a location that provides a clear view of the entire hazardous zone
and it cannot be activated from within the hazardous zone.
Safety distance has been calculated. Calculated distance: S = ( ) mm
The actual distance is equal to or greater than the calculated distance. Actual distance = ( ) mm
Reflective surfaces are not installed in prohibited zones.
Not installed in a reflective configuration.
When muting function is used, a muting sensor must be installed so that muting state should not occur
when a human body enters a detection zone of F3SJ-B-02TS by mistake.
When muting function is used, a muting sensor must be installed so that muting state should not occur
when a human body enters a hazardous zone of a machine.
When muting function is used, muting state can be checked from where a worker operates or adjust the
machine.
A muting sensor consists of two independent devices.
Not used in flammable or explosive atmosphere.
- Wiring Check Before Power Is Turned ON
Sharing the power supply with other devices may cause the F3SJ-B-02TS to be affected by noise or volt-
age drop. It is recommended that this safety component use a dedicated power supply but do not share
with other devices.
The power supply unit provides 24 VDC while complying with the EMC Directive, Low Voltage Directive,
output holding specification.
The power supply polarity is not connected in reverse.
Emitter/receiver cables are properly connected to the respective emitters/receivers.
Double insulation is provided between input/output and hazardous voltage (commercial power source,
etc.).
Outputs are not short-circuited to +24 V line.
Loads are not connected to the +24 V line.
All lines are not connected to commercial power source.
Model of emitter and receiver must be the same.
When two or more sets of F3SJ-B-02TSs are used, they are series-connected or mutual interference pre-
vention measures are taken.
When two or more sets of F3SJ-B-02TSs are used in series connection, sensors other than the F3SJ-B-
02TS must not be connected.
A secondary sensor farthest from its power supply has either of the following:
• Cap
• Key cap for muting
Neither connector nor bracket must be loose.
Auxiliary output must not be used as safety output.
Power supply's 0 V must be grounded.
Wiring must not be bent, cracked, nor damaged.
-Operation Check While the Machine Is Stopped
The test rod is not deformed.
Mounting/Beam Alignment
Wiring
Function Selection
Pre-Operation Checklist /
Maintenance Checklists