4-8SectionOffset and Gain Adjustment
100
SHIFT
CONT
#
1
B
0
A
1
B
0
A
2
C
MONTR
10102 c108
^OFF 0000
The bit will remain ON until the output becomes an appropriate value, at
which time, it will turn OFF.
PLAY
SET
10102 c108
ON FFFF
REC
RESET
10102 c108
OFF FFFF
5. Check the 0V/1V/4mA output, and then turn bit 04 (the Set Bit) of IR word
n+1 ON and then OFF again.
SHIFT
CONT
#
1
B
0
A
1
B
0
A
4
E
MONTR
10104 10102 c108
^OFF ^ OFF FFFF
PLAY
SET
10104 10102 c108
ON ^ OFF FFFF
REC
RESET
10104 10102 c108
OFF ^ OFF FFFF
While the Offset Bit is ON, the offset value will be saved to the Unit’s EE-
PROM when the Set Bit turns ON.
6. To finish the offset adjustment, turn OFF bit 00 (the Offset Bit) of IR word
n+1.
SHIFT
CONT
#
1
B
0
A
1
B
0
A
0
A
MONTR
10100 10104
^ ON ^OFF
PLAY
SET
10100 10104
OFF ^OFF
Caution Do not turn OFF the power supply or restart the Unit while the Set Bit is ON (data
is being written to the EEPROM). Otherwise, illegal data may be written in the
Unit’s EEPROM and “Special I/O Unit Errors” may occur when the power supply
is turned ON or when the Unit is restarted, causing a malfunction.
When making adjustments, be sure to perform both the offset adjustment and
gain adjustment.
Note The EEPROM can be overwritten 50,000 times.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C200H-AD003 and is the answer not in the manual?

Omron SYSMAC C200H-AD003 Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C200H-AD003
CategoryI/O Systems
LanguageEnglish

Related product manuals