13
3-2 Bit Allocation
Direction Word Bit
no. 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Output n Tempera-
ture speci-
fication
Temperature specification
code no.: 00 through 25
Data
hold
enable x 10
1
x 10
0
Input n + 1 Code
0: positive
Conversion data of Input 1
1: negative x 10
3
x 10
2
x 10
1
x 10
0
n + 2 Code
0: positive
Conversion data of Input 2
1: negative x 10
3
x 10
2
x 10
1
x 10
0
n + 3 Code
0: positive
Conversion data of Input 3
1: negative x 10
3
x 10
2
x 10
1
x 10
0
n + 4 Code
0: positive
Conversion data of Input 4
1: negative x 10
3
x 10
2
x 10
1
x 10
0
n + 5
Running
Temperature specification
code no.: 00 through 25
Data
inval-
id
Stand
by for
Memory
error
Disconnection
detected
Setting
error
x 10
1
x 10
0
set-
ting
Input
4
Input
3
Input
2
Input
1
Note n = 100 + 10 x unit no.
The four words from words n+6 through n+9 can be used as work bits. Refer
to the C200H Operation Manual for details.
IR Bit Allocation
IR Name Function
Word Bit
Output n 00 Data hold When this bit is turned ON, conversion of the temperature input
data is stopped and data is returned to its status just prior to turning the
bit ON. When this bit is turned OFF, the temperature input data is
converted to BCD data in cycles.
01
through
07
--- Always turned OFF.
08
through
13
Temperature
specification
code number
These bits specify the temperature specification code number of the
temperature sensing element used in the Unit. A total of 41 code
numbers (thermocouple K (CA) = 11, thermocouple J (IC) = 4, L(Fe-CuNi)
= 4, platinum RTD JPt = 11, platinum RTD Pt= 11 numbers) can be
specified in 2-digit BCD from 00 through 25. (Refer to pages 3 and 16 for
details.) The temperature specification code number becomes valid after
the temperature specification setting flag (word n bit 15) is turned ON.
14 --- Not used. Always turned OFF.
15 Temperature
specification
enable
When this bit is turned ON, the temperature specification code number
specified for word n bits 08 through 13 becomes valid. Be sure to confirm
beforehand that the temperature specification switch (pin 3) on the back
panel has been set to the ON position and that the setting standby flag
(word n+5 bit 06) has also been turned ON. Otherwise the code number
is invalid.
Bit Allocation Section 3-2

Other manuals for Omron SYSMAC C200H

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C200H and is the answer not in the manual?

Omron SYSMAC C200H Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C200H
CategoryController
LanguageEnglish

Related product manuals