The
high
engine
temperature
shutdown
system
will
not
oper¬
ate
if
the
coolant
level
is
too
low.
The
high
engine
temperature
sensor
monitors
coolant
temper¬
ature.
Loss
of
coolant
will
prevent
sensor
opera¬
tion
and
allow
the
engine
to
overheat
causing
severe
damage
to
the
engine.
Therefore,
maintain
adequate
coolant
level
to
ensure
the
operation
of
the
high
engine
temperature
shutdown
system.
•
Low
Coolant
Level
Shutdown
(Optional)
-
A
float
actuated
switch
provides
engine
shutdown
if
cool¬
ant
level
falls
too
low.
Italso
turns
on
the
high
engine
temperature
fault
lamp.
STARTING
The
following
sections
cover
the
three
systems
used
to
start
the
generator
set.
Starting
at
Control
Panel
Move
the
Run-Stop-Remote
switch
on
the
DC
panel
(Figure
1)
to
the
RUN
position.
This
will
activate
the
engine
control
system
and
the
starting
system.
The
star¬
ter
will
begin
cranking
and
after
a
few
seconds
the
engine
should
start.
The
starter
will
disconnect
when
the
engine
reaches
a
speed
of
450
to
570
r/min.
If
the
engine
does
not
start,
the
starter
will
disengage
after
a
specified
period
of
time
and
the
control
will
indi¬
cate
an
overcranK
faull.
Generator
sets
with
the
stand¬
ard
overcrank
control
will
crank
continuously
for
up
to
75
seconds
before
disengaging
the
starter.
Generator
sets
with
the
cycle
cranking
option
will
crank
for
15
seconds
and
then
stop
for
15
seconds
until
3
cycles
have
been
completed
To
clear
an
o
vercrank
fault,
place
the
Run-Stop-Remote
switch
>n
the
STOP
position
and
momentarily
depress
the
Reset
switch.
Wait
two
min¬
utes
for
the
starter
motor
to
cool
and
then
repeat
the
starting
procedure.
If
the
engine
does
not
run
after
a
second
attempt
at
starting,
refer
to
the
Troubleshooting
section.
Starting
From
Remote
Location
Move
the
Run-Stop-Remote
switch
on
the
generator
set
DC
panel
to
the
REMOTE
position.
This
allows
the
generator
set
to
be
started
from
a
remote
switch.
Clos¬
ing
the
remote
switch
initiates
the
starting
sequence
described
in
the
previous
section.
Automatic
Starting
Place
the
Run-Stop-Remote
switch
on
the
generator
set
DC
panel
in
the
REMOTE
position
if
an
automatic
transfer
switch
is
used.
This
allows
the
transfer
switch
to
start
the
generator
set
if
a
power
outage
occurs
and
stop
it
when
the
power
returns.
STOPPING
Before
Stopping
Run
the
generator
set
at
no
load
for
three
to
five
minutes
before
stopping.
This
allows
the
lubricating
oil
and
engine
coolant
to
carry
heat
away
from
the
combustion
chamber
and
bearings.
To
Stop
If
the
set
was
started
at
the
set
control
panel
or
at
a
remote
control
panel,
move
the
Run/Stop/Remote
switch
or
remote
starting
switch
to
the
STOP
position.
If
the
set
was
started
by
an
automatic
transfer
switch,
the
set
will
automatically
stop
about
15
minutes
after
the
normal
power
source
returns.
BREAK-IN
Drain
and
replace
the
crankcase
oil
after
the
first
50
hours
of
operation
on
new
generator
sets.
Refer
to
the
MAINTENANCE
section
of
this
manual
for
the
recom¬
mended
procedures,
NO-LOAD
OPERATION
Periods
of
no
load
operation
should
be
held
to
a
min¬
imum.
If
it
is
necessary
to
keep
the
engine
running
for
long
periods
of
time
when
no
electric
output
is
required,
best
engine
performance
will
be
obtained
by
connect¬
ing
a
“dummy”
electrical
load.
Such
a
load
could
consist
of
heater
element,
etc.
EXERCISE
PERIOD
Generator
sets
on
continuous
standby
must
be
able
to
go
from
a
cold
startto
being
fully
operational
in
a
matter
of
seconds.
This
can
impose
a
severe
burden
on
engine
parts.
Regular
exercising
keeps
engine
parts
lubricated,
pre¬
vents
oxidation
of
electrical
contacts
and
in
general
helps
ensure
reliable
engine
starting.
Exercise
the
generator
set
at
least
once
a
week
for
a
minimum
of
30
minutes
with
load
so
the
engine
reaches
normal
operat¬
ing
temperatures.
Onan
automatic
transfer
switches
have
as
an
option
an
exerciser
that
can
be
preset
to
provide
regular
exercise
periods.
Typically
the
exerciser
can
be
set
for
time
of
start,
length
of
run,
and
day
of
week.
ACAUTION
8