HI
ENG
TEMP
(red)
indicates
engine
has
shut
down
because
of
critically
high
temperature.
OVERSPEED
(red)
indicates
engine
has
shut
down
because
of
excessive
speed.
OVERCRANK
(red)
indicates
the
starter
has
been
locked
out
because
of
excessive
cranking
time.
FAULT
1
(red)
an
undedicated
fault.
May
be
factory
programmed
as
a
shutdown
or
non-shutdown,
and
as
a
timed
or
non-timed
(normally
set
for
timed
shutdown).
®
FAULT
2
(red)
same
features
as
Fault
1
(normally
set
for
timed
shutdown).
LO
ENG
TEMP
(yellow)
engine
temperature
is
margi¬
nally
low
for
starting.
Indicates
inoperative
coolant
heater,
(Lamp
lights
when
engine
water
jacket
temperature
is
70°F
(21
°C)
or
lower.
Since
the
lamp
goes
out
after
the
engine
warms
up
there
should
be
no
cause
for
alarm
even
during
initial
generator
set
operation.)
LO
FUEL
(yellow).
Indicates
fuel
supply
is
marginally
low.
SWITCH
OFF
(flashing
red)
indicates
generator
set
is
riot
in
automatic
start
operation
mode.
AC
Panel
AC
Voltmeter
(Optional):
Dual
range
instrument
indicat¬
ing
AC
voltage
Measurement
range
in
use
shown
on
indicator
light.
AC
Ammeter
(Optional):
Dual
range
instrument
indi¬
cates
AC
generator
line
current.
Wattmeter
(Optional):
Continuously
gives
reading
of
the
generator
output
in
kilowatts.
Frequency
Meter
(Optional):
Indicates
generator
output
frequency
in
hertz.
It
can
be
used
to
check
engine
speed
(each
hertz
equals
30
r/rnin).
Voltage
Adjust
(Optional):
Rheostat
providing
approx¬
imately
plus
or
minus
five
percent
adjustment
of
the
rated
output
voltage.
Upper
and
Lower
Scale
Indicator
Lamps
(Optional):
Indicates
which
scale
to
use
on
the
AC
voltmeter
and
ammeter
Phase
Selector
Switch
(Optional):
Selects
phases
of
generator
output
to
be
measured
by
AC
voltmeter
and
AC
ammeter.
CONTROL
PANEL
INTERIOR
Generator
AC
Voltage
Regulator
The
solid-state
regulator
(VRAS-2)
controls
AC
output
voltage
from
the
generator
at
a
predetermined
level
regardless
of
load.
Voltage
regulation
is
plus
or
minus
two
percent
from
no
load
to
full
load.
Random
voltage
variation
is
pius
or
minus
one
percent
for
constant
loads.
Engine
Control
Module
Electronic
and
relay
components
of
the
engine
monitor¬
ing
circuit
are
on
a
circuit
board
assembly.
Sensor
inputs
(Figure
3)
are
connected
by
the
wiring
harness
to
plug
connectors
on
the
board.
The
control
module
pro¬
vides
the
following
functions
of
unit
protection.
Overcrank
-
Limits
engine
cranking
to
75
seconds.
If
engine
fails
to
start,
the
module
lights
a
fault
lamp
and
opens
the
cranking
circuit.
The
cycle
cranking
option
allows
three
15-second
cranking
cycles
with
two
15-second
rest
periods
on
the
12-lamp
control.
Overspeed
-
Shuts
down
the
engine
immediately
if
overspeed
occurs
and
lights
a
fault
lamp.
The
sen¬
sor
switch
is
mounted
in
'he
end
bell
on
the
genera¬
tor
shaft.
It
is
factory
adjusted
to
shut
down
60
hertz
units
at
2100
±
90
r/rnin,
50
hertz
units
at
1850
±
50
r/min.
Low
Oil
Pressure
-
Shuts
down
the
engine
imme¬
diately
if
oil
pressure
drops
below
14
psi
(97
kPa)
and
lights
a
fault
lamp.
The
fault
is
time-delayed
about
10
seconds
following
starter
disconnect
and
inhibited
during
cranking.
The
delay
allows
oil
pres¬
sure
to
rise
to
normal
before
the
electronic
control
module
monitors
this
system.
A
pre-low
oil
pressure
sensor
and
lamp
(used
with
optional
12-lamp
system)
provides
an
alarm
that
oil
pressure
is
marginally
low,
20
psi
(137
kPa)
or
less.
The
cause
should
be
found
and
corrected
as
soon
as
possible.
High
Engine
Temperature
-
shuts
down
the
engine
immediately
if
coolant
temperature
rises
above
215°F
(102°C)
and
lights
a
fault
lamp.
The
fault
is
time-delayed
about
10
seconds
following
starter
disconnect
and
inhibited
during
cranking.
This
delay
allows
coolant
in
a
hot
engine
time
to
circulate
and
return
the
water
jacket
to
normal
before
the
electronic
control
module
monitors
this
system.
A
pre-high
engine
temperature
sensor
and
lamp
used
with
optional
12-lamp
systems,
provides
an
alarm
that
engine
temperature
is
marginally
high,
205°F
(97°C).
The
cause
should
be
found
and
cor¬
rected
as
soon
as
possible.
Field
Breaker:
Provides
generator
exciter
and
regulator
protection
from
overheating
in
the
event
of
certain
fail¬
ure
modes
of
generator,
exciter
and
voltage
regulator.
6