Installing
13
z
When two or more drivers are installed
When two or more drivers are installed side by side, provide 20mm
(0.79 in.) and 25 mm (0.98 in.) clearances in the horizontal and
vertical directions, respectively.
in horizontal direction
25 mm (0.98 in.) or mor
in vertical direction
z
When drivers are installed in a close contact state
Install drivers to a at metal plate oering high heat
conductivity [corresponding to an aluminum plate of
350×350×2 mm (13.78x13.78x0.08 in.) or larger].
Operating ambient temperature
30 W, 60 W, 120 W: 0 to +50 °C (+32 to +122 °F)
200 W, 300 W, 400 W : 0 to +40 °C (+32 to +104 °F)
When a driver is installed to a DIN rail
Use the DIN rail mounting plate
MADP02
(sold separately), and
install it to a 35 mm (1.38 in.) wide DIN rail.
After installing to the DIN rail, secure the both sides of the driver
with end plates that the customer provides.
Refer to "
MADP02
handling guideline" for installation method.
Operating ambient temperature: 0 to +40°C (+32 to +104 °F)
DIN rail
z
When drivers are installed in a close contact state
*
*
300 W type drivers of single-phase 200-240 VAC cannot be
installed in a close contact state.
When installing two or more drivers, provide a clearance of
20mm (0.79 in.) between them in the horizontal direction.
in horizontal direction
Dimensions
[Unit: mm (in.)]
Mass: 0.8 kg (1.76 lb.)
40
(
1.57
)
4.5
(
0.18
)
4.8
(
0.19
)
9.5
(
0.37
)
120
(
4.72
)[
50
(1.97)]
5
(
0.20
)
23
(
0.91
)
max.
150
(
5.91
)
5
(
0.20
)
18
(0.71)
11
(
0.43
)
9
(
0.35
)
89
(
3.50
)
36.5
(
1.44
)
5
(
0.20
)
(
1.18
)
R2.25
(
0.089
3×M3
ϕ
4.5
(ϕ
0.177
)
Thru
Protective Earth Terminal2×M4