Connecting
23
Connection example for I/O signals and programmable controller
z
Sink logic
24 VDC
CN5
4.5 to 30 VDC
100 mA or less
IN-COM0
IN0
IN1
IN2
IN3
IN4
IN5
IN6
IN-COM1
OUT0+
OUT0
-
OUT1+
OUT1
-
100 mA or less
0 V
2
1
3
4
5
6
7
6.6 k
6.6 k
6.6 k
6.6 k
6.6 k
6.6 k
1 k
1 k
1 k
1 k
1 k
1 k
8
6.6 k
1 k
15
R
R
17
16
18
Programmable controller Driver
9
0 V
Do not connect anything.
Recommended resistance value when the current limiting resistor R is connected
In the case of 24 VDC: 680 to 2.7 k (2 W) In the case of 5 VDC: 150 to 560 (0.5 W)
z
Source logic
24 VDC
CN5
4.5 to 30 VDC
100 mA or less
100 mA or less
0 V
2
1
3
4
5
6
7
6.6 k
6.6 k
6.6 k
6.6 k
6.6 k
6.6 k
1 k
1 k
1 k
1 k
1 k
1 k
8
6.6 k
1 k
15
R
R
17
16
18
Programmable controller Driver
9
0 V
IN-COM0
IN0
IN1
IN2
IN3
IN4
IN5
IN6
IN-COM1
OUT0+
OUT0
-
OUT1+
OUT1
-
Do not connect anything.
Recommended resistance value when the current limiting resistor R is connected
In the case of 24 VDC: 680 to 2.7 k (2 W) In the case of 5 VDC: 150 to 560 (0.5 W)
Note
Use output signals at 4.5 VDC to 30 VDC.
Be sure to use the current of the OUT0 and OUT1 at 100 mA or less. If the current exceeds this value, connect the
current limiting resistor R.
Pass the current of 5 mA or more for the SPEED-OUT output.
Do not connect anything to the pin No. 9 when using an external power supply.