VCCX2 Controller Technical Guide
BACnet
®
Properties for the VCCX2 Controller
Parameter Object Description
Limits
Refrigerant
Module 1
Relay 1
BI: 84 Current Status of
Compressor A1 Enable
Relay.
Refrigerant
Module 1
Relay 2
BI: 85 Current Status of
Compressor A2 Enable
Relay.
Refrigerant
Module 1
Relay 3
BI: 86 Current Status of
Condenser 1 Enable Relay.
Refrigerant
Module 1
Relay 4
BI: 87 Current Status of
Relay #4
Refrigerant
Module 1
Relay 5
BI: 88 Current Status of
Relay #5
B1
Compressor
Enable
BI: 89 Current Status of Enable
Signal to Compressor B1
B2
Compressor
Enable
BI: 90 Current Status of Enable
Signal to Compressor B2
B1
Compressor
Alarms
BI: 91 Indicates an RSM alarm is
present on the B1 circuit.
B2
Compressor
Alarms
BI: 92 Indicates an RSM alarm is
present on the B2 circuit.
B1-2 Defrost
Switch
BI: 93 Outside Coil B1/B2 Temp
Switch for Defrost Mode
B1-2 Water
Proof of Flow
BI: 94 B1/B2 Switch for Water
Proof of Flow
B1-4
Emergency
Shutdown
(RSMD)
BI: 95 Emergency Shutdown Input
on Module B
Refrigerant
Module 2
Relay 1
BI: 96 Current Status of
Compressor 1 Enable Relay.
Refrigerant
Module 2
Relay 2
BI: 97 Current Status of
Compressor 2 Enable Relay.
Refrigerant
Module 2
Relay 3
BI: 98 Current Status of
Condenser 1 Enable Relay.
Refrigerant
Module 2
Relay 4
BI: 99 Current Status of
Relay #4
Refrigerant
Module 2
Relay 5
BI: 100 Current Status of
Relay #5
C1
Compressor
Enable
BI: 101 Current Status of Enable
Signal to Compressor C1
C2
Compressor
Enable
BI: 102 Current Status of Enable
Signal to Compressor C2
BACnet
®
Properties for the VCCX2 Controller
Parameter Object Description
Limits
C1
Compressor
Alarms
BI: 103 Indicates an RSM alarm is
present on the C1 circuit.
C2
Compressor
Alarms
BI: 104 Indicates an RSM alarm is
present on the C2 circuit.
C1-2 Defrost
Switch
BI: 105 Outside Coil C1/C2Temp
Switch for Defrost Mode
C1-2 Water
Proof of Flow
BI: 106 C1/C2 Switch for Water
Proof of Flow
C1-4
Emergency
Shutdown
(RSMD)
BI: 107 Emergency Shutdown Input
on Module C
Refrigerant
Module 3
Relay 1
BI: 108 Current Status of
Compressor 1 Enable Relay.
Refrigerant
Module 3
Relay 2
BI: 109 Current Status of
Compressor 2 Enable Relay.
Refrigerant
Module 3
Relay 3
BI: 110 Current Status
Condenser 1 Enable Relay.
Refrigerant
Module 3
Relay 4
BI: 111 Current Status of
Relay #4
Refrigerant
Module 3
Relay 5
BI: 112 Current Status of
Relay #5
D1
Compressor
Enable
BI: 113 Current Status of Enable
Signal to Compressor D1
D2
Compressor
Enable
BI: 114 Current Status of Enable
Signal to Compressor D2
D1
Compressor
Alarms
BI: 115 Indicates an RSM alarm is
present on the D1 circuit.
D2
Compressor
Alarms
BI: 116 Indicates an RSM alarm is
present on the D2 circuit.
D1-2 Defrost
Switch
BI: 117 Outside Coil D1/D2 Temp
Switch for Defrost Mode
D1-2 Water
Proof of Flow
BI: 118 D1/D2 Switch for Water
Proof of Flow
D1-4
Emergency
Shutdown
(RSMD)
BI: 119 Emergency Shutdown Input
on Module D
Refrigerant
Module 4
Relay 1
BI: 120 Current Status of
Compressor 1 Enable Relay
Refrigerant
Module 4
Relay 2
BI: 121 Current Status of
Compressor 2 Enable Relay
Refrigerant
Module 4
Relay 3
BI: 122 Current Status of
Condenser 1 Enable
Relay
APPENDIX C
-
VCCX2 BACnet
®
VCCX2 BACnet
®
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Orion Control Systems AAON VCCX2 and is the answer not in the manual?

Orion Control Systems AAON VCCX2 Specifications

General IconGeneral
BrandOrion Control Systems
ModelAAON VCCX2
CategoryController
LanguageEnglish

Related product manuals