– 17 –
MAC9512086C2
CS-A73KE
Operation Details
Compressor
restarts
(3 minutes waiting)
Compressor
OFF
➡➡
Comp. operates for 50 secs.
and
Fan Motor OFF
• After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and
restart automatically. (Time Delay Safety Control is valid).
• If the above phenomenon is repeated for 3 times, the compressor will stops.
• The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
Compressor Protection Control
Automatic Fan Speed Mode
* 1 Fan Speed is Hi until the compressor stops (when the room temperature reaches
setting temperature).
* 2 Fan Speed is Me after the compressor restarts.
* SLo: Indoor Fan rotates at 4 second intervals at low speed.
Indoor
Fan
Comp.
SLo SLo SLo SLo
ON ONOFF
stop stop stop
30"
stop
30"160"
1
40"
40"
20"
✕
.
.
.
.
2
✕
.
.
.
.
When Automatic Fan Speed is selected at Remote Control during cooling operation.
• Fan speed rotates in the range of Hi to Me.
• Deodorizing Control.
Untitled-9 6/19/00, 11:00 AM17