– 37 –
MAC9512086C2
CS-A73KE
4 Balance refrigerant of the 2-way, 3-way valves
(Lack of refrigerant in the refrigeration cycle)
(Indoor unit)
(Liquid side)
(Gas side)
OPEN
CLOSE
Lo Hi
Refrigerant
Reclaiming
Equipment
3-way valve
Open
2-way valve
Open
(Outdoor unit)
Procedure:
(1) Confirm that both the 2-way and 3-way valves are
set to the open position.
(2) Connect the charge set to the 3-way valve’s
service port.
Leave the valve on the charge set closed.
Connect the charge hose with the push-pin to the
service port.
(3) Connect the charge set’s centre hose to refriger-
ant reclaiming equipment.
Purge the air from charge hose.
(4) Open the valve (Low side) on the charge set
and discharge the refrigerant until the gauge
indicates 0.05 MPa (0.5 kg/cm
2
G) to 0.1 MPa
(1 kg/cm
2
G).
If there is no air in the refrigeration cycle (the pressure
when the air conditioner is not running is higher than
0.1 MPa (1 kg/cm
2
G), discharge the refrigerant until
the gauge indicates 0.05 MPa (0.5 kg/cm
2
G) to 0.1
MPa (1 kg/cm
2
G). If this is the case, it will not be
necessary to apply a evacuation.
Discharge the refrigerant gradually; if it is discharged
too suddenly, the refrigeration oil will also be dis-
charged.
(5) Turn on refrigerant reclaiming equipment .
Untitled-13 6/19/00, 11:15 AM37