8.1.5. Heating Operation
8.1.5.1. Thermostat control
- Compressor is OFF when Intake Air Temperature - Internal Setting
> +1.5°C.
- Compressor is ON after waiting for 3 minutes, if the Intake Air
Temperature - Internal Setting Temperature < Compressor OFF
point -0.5°C.
8.1.6. Automatic Operation
This mode can be set using remote control and the operation is decided by remote control
setting temperature, indoor intake air temperature and outdoor air temperature.
During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor
are running for 30 seconds to detect the indoor intake and outdoor air temperature. The
operation mode is decided based on below chart.
Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below
table. After the adjustment of T1, T2 and T3 values, the operation mode for that particular
environment and remote control setting is judged and performed,based on the above operation
mode chart, every 30 minutes.