– 44 –
MAC9509078C2
Operation Details
CS-G93KE
g. Minimum Frequency Operation Protection
When the compressor operates at less than 31 Hz for 40 minutes, the operating frequency will increase to
31 Hz for 2 minutes.
40 min
Comp. Operating
Frequency
31Hz
2 min
i. Low Power Supply Voltage Protection
When the DC voltage supplied to IPM (Power transistor) is reduced to 169 ± 5V (CS-G93KE) or 160 ± 5V
(CS-G123KE) the compressor stops and restarts after 3 minutes.
If within 30 seconds after restarting of compressor, the DC voltage is reduced to 169 ± 5V (CS-G93KE) or
160 ± 5V (CS-G123KE) again, the compressor will stop for 1 minute.
If this condition repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and
F99 is displayed.
j. High Power Supply Voltage Protection
When the voltage supply (AC) exceeds 295 ± 15 V (T
0
), the air conditioner stops and restarts automatically
when the voltage supply (AC) is below (T
0
- 5)V. However, waiting for 3 minutes is necessary for re-operation.
DC Voltage
Supplied to IPM
(V)
169 or 160
Comp OFF
Comp
OFF
30 sec30 sec1 min
7 times
30 sec3 min
TIMER LED
Blinks
F99 is
displayed
h. Low Frequency Operation Protection
When the above conditions occur, the compressor will operate at minimum frequency as below:-
Cooling / Soft Dry
Heating
CU-G93KE
Min 31Hz
Min 33Hz
CU-G123KE
Min 31Hz
Min 36Hz
28°C or < 14°C
24°C or < 4°C
> 0°C
Heating
30°C or < 15°C
38°C or < 16°C
< 30°C
Cooling/Soft Dry
Indoor intake air temp. (°C)
Outdoor air temp. (°C)
Indoor heat exchanger temp. (°C)
Operation
< 30 sec < 30 sec1 min < 30 sec
Untitled-6 6/20/00, 5:13 PM44