Operation Details
CS-G93KE
c. Anti-Fog Discharge Control
• The compressor operating frequency is regulated by operation time to prevent fog discharged from indoor
unit as shown in the table below.
Operation
Time, T (min)
Compressor operating frequency
50Hz
46Hz
43Hz
0 ≤ T < 30
30 ≤ T < 90
T ≥ 90
Note: • Indoor fan is running at Me- or below.
• After 420 minutes from the start of operation, the operation timer counting is restarted from “0”.
Model No.
CU-G93KE CU-G123KE
d. High Pressure Control at Minimum Frequency Control
• When the outdoor air temperature increases to 38.6°C, compressor operating frequency reduces to
minimum of 31 Hz. Compressor operating frequency will resume to normal when outdoor air temperature
decreases to 37.8°C.
70Hz
64Hz
58Hz