Outdoor Unit
To protect compressor from reverse
rotation when there is a instantaneous
power failure.
60 Secs. Forced Operation Control
Once the compressor is activated, it
does not stop within the first 60 secs.
However, it stops immediately with
remote control stop signal.
Overload Protector
2-Stage OLP to protect the compressor.
Overload Protector will trip when
Temperature of compressor increases
to 120C.
High temperature or high current flows
to compressor.
(Refer circuit diagram for OLP
characteristic)
Compressor Reverse Rotation
Protection Control
Outdoor Fan Operation Control
There is a service port inside the outdoor
unit. The port can be connected to a
device which controls the outdoor fan
motor when the cooling operation mode
is used in cold winter.
4
CS-PV9CKE CU-PV9CKE / CS-PV12CKE CU-PV12CKE