• Airflow direction (Horizontal, Vertical) Control
o During any operation mode combines with Patrol operation, airflow direction follows respective operation
mode.
o During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button is
pressed, no signal is sent to air conditioner, and no change on LCD display.
o During Patrol individual operation if e-ion stops, Airflow direction louver closed.
• Indicator
o When Patrol is selected, patrol sensor indicator ON.
No Description BLUE ORANGE RED E-ION
1 When patrol function is not selected OFF OFF OFF -
2 During gas sensor error detection control OFF OFF Blinking OFF
3 During stop OFF OFF OFF OFF
4 2 minutes gas sensor initial stabilization time (Level 0) ON OFF OFF OFF
a. Dirtiness level 0* ON OFF OFF OFF
a. Dirtiness level 1 OFF ON OFF OFF
b. Dirtiness level 1* OFF ON OFF ON
5
During operation
During patrol
c. Dirtiness level 2 OFF OFF ON ON
• Remote Control Receiving Sound
o Normal Operation Î Patrol Mode : Beep
o Patrol Mode Î Stop : Long Beep
o Patrol Mode Î Normal Operation : Beep
o Stop Î Patrol : Beep
• Timer Control
o When ON timer activates when unit stops, previous operation resumes and restored last saved Patrol
operation status.
o When ON timer activates during any operation, no change and carry on current operation.
o When OFF timer activates during any operation, all operation stops and the latest Patrol operation status is
saved.
• Power Failure Control
o During Patrol individual operation, if power failure occurs, after power resumes, Patrol individual operation
resumes immediately.
o During combination operation, if power failure occurs, after power resumes combination operation resume
immediately.