11.1.3.2 Automatic Operation
• This mode can be set using remote control and the operation is decided by remote control setting temperature,
remote control operation mode and indoor intake air temperature.
• During operation mode judgment, indoor fan motor (with speed of Lo-) is running for 30 seconds to detect the
indoor intake air temperature.
• Every 10 minutes, the indoor temperature is judged.
• For the 1st judgment
o If indoor intake temperature - remote control setting temperature 2°C, COOL mode is decided.
o If -2°C indoor intake temperature - remote control setting temperature < 2°C, DRY mode is decided.
• For the 2nd judgment onwards
o If indoor intake temperature - remote control setting temperature 3°C, if previous operate in DRY mode,
then continue in DRY mode. Otherwise COOL mode is decided.
o If -2°C indoor intake temperature - remote control setting temperature < 3°C, maintain with previous mode.
11.1.3.3 Fan Operation
• Fan operation is used to circulate air in the room.
• During operation, indoor fan run continuously but outdoor fan and compressor stop.
• Temperature setting is not applicable.
11.2 Indoor Fan Motor Operation
A. Basic Rotation Speed (rpm)
• Manual Fan Speed
[Cooling, Dry]
o Fan motor’s number of rotation is determined according to remote control setting.
Remote control
Tab Hi Me+ Me Me- Lo
• Auto Fan Speed
[Cooling, Dry]
o According to room temperature and setting temperature, indoor fan speed is determined automatically.
o The indoor fan will operate according to pattern below.