12.2.6 Odor Cut Control
To reduce the odor released from the unit.
o Start Condition
AUTO FAN Speed is selected during COOL or DRY operation.
During freeze prevention control and timer preliminary operation, this control is not applicable.
o Control content
Depends on compressor conditions:
1. Compressor OFF Compressor ON.
The indoor unit fan stops temporarily and then starts to blow at minimum airflow for 30 seconds.
2. Compressor ON Compressor OFF.
The indoor unit fan stops for 90 seconds and then blows at minimum airflow for 20 seconds.
12.2.7 Demand Control
When the air-conditioner connected to Demand Response Enabling Devices (DRED), the power consumption
especially during peak hours could be controlled.
DRM1
Relay 1
DRED AIR CONDITIONER
DRM2
Relay 2
DRM3
Relay 3
COM
Three Demand response modes (DRM) are available
o DRM1 = Compressor cut off
o DRM2 = Operate at 50% of rated input power
o DRM3 = Operate at 75% of rated input power
During DRM
, the Power Indicator blinks (3 seconds ON and 0.5 seconds OFF) to indicate the compressor cut
off status.
12.2.8 Pump down Operation by CN-S
A convenience method to activate pump down operation.
Control start condition:
o During power standby condition, short CN-S continuously between 1 second and 10 seconds.
Control stop condition:
o 480 seconds after pump down operation starts.
o CN-S is shorted again during pump down operation.