15.2. COOLING PERFORMANCE
CS-W34BB4P
Model Cooling capacities are based on conditions below.
CS-W34BB4P
● 1 phase, 50Hz, 400V
● Indoor temperature 27°C D.B.T., 19°C W.B.T.
● Outdoor temperature 35°C D.B.T.
● Standard air volume 23m
3
/min
Cooling capacity 10.0 kW
Cooling capacity Cooling power consumption
Indoor Air Temp. Outdoor Temperature (°C D.B.T.) Indoor Air Temp. Outdoor Temperature (°C D.B.T.)
25 30 35 40 43 25 30 35 40 43
TC TC TC TC TC IPT IPT IPT IPT IPT
D.B.T. W.B.T. kW kW kW kW kW D.B.T. W.B.T. kW kW kW kW kW
17 10.51 9.90 9.41 8.70 8.19 17 3.04 3.39 3.64 4.05 4.24
23 19 10.99 10.65 10.11 9.42 8.94 23 19 3.27 3.55 3.86 4.24 4.49
22 12.00 11.68 11.15 10.43 9.94 22 3.54 3.83 4.17 4.58 4.85
17 10.29 9.89 9.32 8.64 8.15 17 3.09 3.34 3.64 3.97 4.21
25 19 11.01 10.63 10.05 9.36 8.87 25 19 3.29 3.56 3.87 4.23 4.48
22 12.00 11.63 11.06 10.31 9.84 22 3.56 3.84 4.18 4.57 4.84
17 10.16 9.77 9.22 8.57 8.11 17 3.10 3.34 3.63 3.95 4.18
27 19 11.02 10.65 10.00 9.25 8.95 27 19 3.31 3.57 3.88 4.22 4.47
22 11.99 11.59 10.98 10.20 9.75 22 3.57 3.85 4.19 4.55 4.83
17 10.14 9.77 9.20 8.64 8.21 17 3.08 3.33 3.59 3.85 4.02
29 19 11.00 10.60 10.00 9.37 8.91 29 19 3.29 3.56 3.83 4.12 4.29
22 11.94 11.53 10.91 10.21 9.74 22 3.62 3.92 4.22 4.53 4.72
17 10.12 9.78 8.55 8.69 8.28 17 3.06 3.32 3.56 3.79 3.90
32 19 10.98 10.60 10.01 9.42 8.98 32 19 3.27 3.55 3.80 4.05 4.17
22 12.01 11.40 10.90 10.22 9.84 22 3.55 3.87 4.24 4.52 4.76
37