EasyManua.ls Logo

Panasonic CS-W34BB4P

Panasonic CS-W34BB4P
113 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25.10. Indoor unit fan control
1. Fixing at LO, MED or HI
When LO, MED or HI is set, the relay switches and operation is carried out at that setting.
2. Automatic fan speed
When set to AUTO, the indoor unit fan operation changes as shown in the table below.
(Indoor temperature) - (Setting temperature) (Units: K)
Mode / Fan Speed HI MED LO
Cooling +3 or higher +1.5 ~ 3 Less than +1.5
Heating -3 or lower -1.6 ~ - 3 More than -1.5
Fan MED irrespective of temperature
68

Related product manuals