<When hot start operation is cancelled by time>
26.5. Indoor unit fan control when thermostat is off during heating mode
operation
When the thermostat of the indoor unit turns off during heating mode operation, the indoor unit fan operates for 2 minutes at LOW
and then stops. In addition, 5 minutes after the thermostat of the indoor unit turns off, the indoor unit fan operates at LOW for 10
seconds, and at 3 minutes interval after that, it switches back to LOW operation for another 10 seconds.
26.6. Excess heat dissipation for indoor unit
The indoor unit fan continue its operation for 30 seconds after heating mode operation turns off in order to dissipate excess heat.
1. When heating mode operation has stopped
(LOW speed for 30 seconds)
2. When operation is set to a mode other than heating by means of the OPERATION button
3. If operation starts again during the 30 seconds mentioned at (1)
(The fan operates at LOW speed for the remainder of the 30 seconds and then hot start commences.)
64