Service data provided are based on the air conditioner running under rated frequency during forced cooling / forced
heating mode.
21.1 Cool Mode Outdoor Air Temperature Characteristic
Condition
- Indoor room temperature: 27°C Dry Bulb/19°C Wet Bulb
- Unit setting: Standard piping length, forced cooling at 16°C, Hi fan
- Compressor frequency: Rated for cooling operation
- Piping length: 5m
- Voltage: 230V
21.1.1 CS-Z25UFEAW CU-Z25UBEA
Indoor Discharge
Air Temperature (°C)
Indoor Discharge
Air Temperature (°C)
Outdoor Air Temperature (°C)
Outdoor Air Temperature (°C)
Outdoor Air Temperature (°C)
Low Pressure (MPa) Current (A)
2.00
2.50
3.00
14 19 24 29 34 39 44
0.90
1.00
1.10
1.20
14 19 24 29 34 39 44
13.00
13.50
14.00
14.50
15.00
15.50
16.00
14
19
24 29 34 39 44
Outdoor Air
Temperature (°C)
16
30
35
43
14.25
14.58
14.70
14.85
Indoor Discharge
Air Temperature (°C)
Outdoor Air
Temperature (°C)
16
30
35
43
2.33
2.46
2.50
2.62
Current
(A)
Outdoor Air
Temperature (°C)
16
30
35
43
1.04
1.06
1.07
1.11
Low Pressure
(MPa)