2. Heating
Note:
a. UP:
If move from Lo, the fan speed will be shifted to Maximum 1,520 rpm.
If move from Maximum, the fan speed no change.
In up zone, 10 rpm is added for every 10s until Maximum 1,520 rpm.
b. DOWN:
The fan speed will be decreased one step every 10 sec. until Minimum 1,270 rpm.
c. Current Output Fixed:
Maintain at present fan speed.
d. Instantaneous Maximum:
Fan speed will be increased to maximum auto fan speed.
e. Temperature in ( ) is for Powerful Mode operation.
C. Fan Motor Control
1. Motor specification
Phase control motor
D. Deodorizing Control
i. Control condition
Control at cooling/soft dry operation and auto fan speed setting.
No Deodorizing Control is performed during ON timer standby operation and during Freeze Prevention Control.
ii. Operation
The odor status is arranged as below and it is shifted as follows.
* When COMP is ON 1
2
3
(Shift to 4 when COMP is OFF)
* When COMP is OFF 4
5
6
7
6
←→
7
(Shift to 1 when COMP is ON)
* Start from 4 if the Thermostat is OFF during the start operation.
67