13.2 Sensible Capacity Chart
CU-E9PFE
220/230/240V Outdoor Temperature
Indoor
wet bulb
30 °C 35 °C 40 °C 46 °C
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0 °C 2.48 1.88 0.51 2.32 1.80 0.55 2.16 1.73 0.58 1.96 1.65 0.63
19.0 °C 2.50 0.56
19.5 °C 2.72 1.97 0.52 2.55 1.89 0.56 2.37 1.82 0.60 2.15 1.73 0.64
22.0 °C 2.97 2.04 0.53 2.77 1.96 0.57 2.58 1.89 0.61 2.35 1.81 0.65
CU-E12PFE
220/230/240V Outdoor Temperature
Indoor
wet bulb
30 °C 35 °C 40 °C 46 °C
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0 °C 3.47 2.63 0.86 3.24 2.52 0.93 3.02 2.43 0.99 2.74 2.30 1.07
19.0 °C 3.50 0.94
19.5 °C 3.81 2.76 0.88 3.56 2.65 0.94 3.31 2.55 1.01 3.01 2.43 1.09
22.0 °C 4.15 2.86 0.89 3.88 2.75 0.96 3.61 2.65 1.03 3.28 2.53 1.11
CU-E18PFE
220/230/240V Outdoor Temperature
Indoor
wet bulb
30 °C 35 °C 40 °C 46 °C
TC SHC IP TC SHC IP TC SHC IP TC SHC IP
17.0 °C 4.96 3.76 1.41 4.64 3.61 1.52 4.31 3.47 1.62 3.92 3.29 1.75
19.0 °C 5.00 1.54
19.5 °C 5.45 3.94 1.44 5.09 3.78 1.55 4.74 3.64 1.65 4.31 3.47 1.78
22.0 °C 5.94 4.08 1.46 5.55 3.93 1.57 5.16 3.79 1.68 4.69 3.61 1.82
TC - Total Cooling Capacity (kW)
SHC - Sensible Heat Capacity (kW)
IP - Input Power (kW)