EasyManua.ls Logo

Panasonic CU-E9GFE-2 - Page 8

Panasonic CU-E9GFE-2
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
Model
Indoor
CS-E12GFEW
CS-E12GFEW-2
Outdoor CU-E12PFE
Performance Test Condition EUROVENT
Power Supply
Phase, Hz Single, 50
V 220 230 240
Min. Mid. Max. Min. Mid. Max. Min. Mid. Max.
Cooling
Capacity
kW 0.85 3.50 3.80 0.85 3.50 3.80 0.85 3.50 3.80
BTU/h 2900 11900 13000 2900 11900 13000 2900 11900 13000
kcal/h 730 3010 3270 730 3010 3270 730 3010 3270
Running Current A – 4.35 – – 4.15 – – 4.00 –
Input Power W 255 940 1.11k 255 940 1.11k 255 940 1.11k
Annual Consumption kWh – 470 – – 470 – – 470 –
EER
W/W 3.33 3.72 3.42 3.33 3.72 3.42 3.33 3.72 3.42
BTU/hW 11.37 12.66 11.71 11.37 12.66 11.71 11.37 12.66 11.71
kcal/hW 2.86 3.20 2.95 2.86 3.20 2.95 2.86 3.20 2.95
ErP
Pdesign kW 3.5
SEER (W/W) 5.8
Annual
Consumption
kWh 211
Class A+
Power Factor % – 98 – – 98 – 98 –
Indoor Noise (H / L / QLo)
dB-A 39 / 28 / 24
Power Level dB 55 / – / –
Outdoor Noise (H / L / QLo)
dB-A 48 / – / –
Power Level dB 63 / – / –
Heating
Capacity
kW 0.85 4.00 6.00 0.85 4.00 6.00 0.85 4.00 6.00
BTU/h 2900 13600 20500 2900 13600 20500 2900 13600 20500
kcal/h 730 3440 5160 730 3440 5160 730 3440 5160
Running Current A – 4.60 – – 4.40 – – 4.20 –
Input Power W 245 1.00k 1.90k 245 1.00k 1.90k 245 1.00k 1.90k
COP
W/W 3.47 4.00 3.16 3.47 4.00 3.16 3.47 4.00 3.16
BTU/hW 11.84 13.60 10.79 11.84 13.60 10.79 11.84 13.60 10.79
kcal/hW 2.98 3.44 2.72 2.98 3.44 2.72 2.98 3.44 2.72
ErP
Pdesign kW 3.2
Tbivalent °C -10
SCOP (W/W) 3.8
Annual
Consumption
kWh 1179
Class A
Power Factor % – 99 – – 99 – 99 –
Indoor Noise (H / L / QLo)
dB-A 39 / 27 / 23
Power Level dB 55 / – / –
Outdoor Noise (H / L / QLo)
dB-A 50 / – / –
Power Level dB 65 / – / –
Low Temp. : Capacity (kW) / I. Power (W) / COP 4.35 / 1.68k / 2.59
Extr Low Temp. : Capacity (kW) / I. Power (W) / COP 3.37 / 1.49k / 2.26
Max Current (A) / Max Input Power (W) 8.70 / 1.90k
Starting Current (A) 4.60