Time Delay Safety Control
Automatic Restarting Control
Anti-freezing Control
If temperature of evaporator is lower than 2°C continuously
for 4 minutes, the compressor ill cease to prevent the
evaporator from freezing. Fan speed setting will not be
changed.
When temperature of evaporator reaches 10°C,
compressor will restart.
During Cooling Mode Operation, the Time Delay Safety Control
is available.
Compressor Protection Control
Anti-reversing Control
7 Operation Details
7.1. Cooling Mode Operation
When selecting the Cooling Mode Operation, the unit will operate according to the setting by the Remote Controller and the
operation is as the following.
3 min. ---- The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor).
7 min. ---- The unit will automatically operate in 7 minutes even if the room temperature is not reached.
(Prevention of raising the humidity)
If the outdoor fan motor does not run 50 seconds after the compressor starts, the compressor will cease and restart in 3
minutes.(Time Delay Safety Control is effective.)
If this symptom occurs repeatedly 3 times, the compressor will stop.
If the operation mode changed or the unit turned off by remote controller, Compressor Protection Control will be reset.
If the compressor has been continuously running for 5 minutes, and the difference of temperature between intake air and
evaporator is continuously lower than 2.5°C or below for 2 minutes, the compressor is ceased for 3 minutes then restarts. (Time
Delay Protection Control is effective.)
14
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5