10.7 Dew Prevention Control
z To prevent dew formation at indoor unit discharge area, the horizontal air vane is automatically set at position 2
(refer to 9.6).
z This control is activated when:-
*Compressor runs continuously for 60 minutes.
*Horizontal air vane is at position 4 or 5 (refer to 9.6).
*Actual fan speed is lower than Lo level.
*Intake air temperature is lower than 29℃
*Intake air temperature changes within 2℃ for more than 30 minutes.
z Dew prevention stops when:-
z Any of the above condition is out of the range described above.
z Operation stops.
z Power OFF.