12
(EN)
Setting
RC. setting mode (Main/sub, Clock type, Password change)
Detailed settings
(Vent output setting, Temp sensor setting, Temp display
setting)
1
Press and hold the 3 buttons for
4 seconds or more simultaneously.
, , ►
2
Select the item to set.
▲ ▼ →
RC. setting mode
3
Set.
(Select the Code no. and Set data.)
▲ ▼ → ► →
(Repeat)
Code no. Set data
Code no.
Set data
01 Main/sub
Set this when using 2 remote controllers.
• 0000: Sub
• 0001: Main (factory
setting)
02 Clock type Set the type of clock display.
• 0000: 24 hours
• 0001: 12 hours
(AM/PM)
2F
Password
change
Set the administrator password.
• 0000 to 9999
• 0000 (factory setting)
Detailed settings
3
Set.
(Select the indoor unit number, Code no. and Set data.)
▲ ▼ → ► →
(Repeat)
Indoor unit
number
Set data
Code no.
Code no.
Set data
31
Vent output
setting
Set this when connecting a commercially sold fan, etc. to the
ventilation fan output “FAN DRIVE:2P (White)” on the indoor control
board.
*Dedicated cables (optional) are required.
• 0000: Not connected
• 0001: Connected
32
Temp sensor
setting
Set this when measuring the room temperature with the room
temperature sensor of the remote controller.
• When using the main and sub controllers, the main one is
enabled.
• When controlling in group, set this for the main indoor unit number.
(No setting is required for sub indoor units.)
• When using with the remote sensor in combination, set the indoor
unit setting data.
• 0000: Indoor unit
• 0001: RC
33
Temp display
setting
Set the type of temperature display.
• 0000: °C
• 0001: °F
業務用リモコンCZ-RTC3据付書En.indd12業務用リモコンCZ-RTC3据付書En.indd12 2014/01/2414:25:072014/01/2414:25:07