12
(EN)
Setting
RC. setting mode (Main/sub, Clock type, Password change)
Detailed settings
(Vent output setting, Temp sensor setting, Temp display
setting)
1
Press and hold the 3 buttons for
4 seconds or more simultaneously.
, ,
2
Select the item to set.
RC. setting mode
3
Set.
(Select the Code no. and Set data.)
(Repeat)
Code no. Set data
Code no.
Set data
01 Main/sub
Set this when using 2 remote controllers.
• 0000: Sub
• 0001: Main (factory
setting)
02 Clock type Set the type of clock display.
0000: 24 hours
• 0001: 12 hours
(AM/PM)
2F
Password
change
Set the administrator password.
0000 to 9999
0000 (factory setting)
Detailed settings
3
Set.
(Select the indoor unit number, Code no. and Set data.)
(Repeat)
Indoor unit
number
Set data
Code no.
Code no.
Set data
31
Vent output
setting
Set this when connecting a commercially sold fan, etc. to the
ventilation fan output “FAN DRIVE:2P (White)” on the indoor control
board.
*Dedicated cables (optional) are required.
0000: Not connected
• 0001: Connected
32
Temp sensor
setting
Set this when measuring the room temperature with the room
temperature sensor of the remote controller.
When using the main and sub controllers, the main one is
enabled.
When controlling in group, set this for the main indoor unit number.
(No setting is required for sub indoor units.)
When using with the remote sensor in combination, set the indoor
unit setting data.
0000: Indoor unit
• 0001: RC
33
Temp display
setting
Set the type of temperature display.
• 0000: °C
• 0001: °F
CZ-RTC3En.indd12業務用リモコンCZ-RTC3据付書En.indd12 2014/01/2414:25:072014/01/2414:25:07