10
DAILY USER´S MANUAL EBL128 VERSION 2.2.X DOCUMENT NUMBER: MEW01786 REVISION: 1
7. DISABLE OR RE-ENABLE (H2)
a) Log on to the c.i.e.
b) Navigate to menu H2.
c) Press "A". The sub menu consists of a list (B1 - B11) in which you can scroll. B1 is displayed.
d) Select a sub menu and press “A”.
7.1. SUB MENU LIST (B1 B11)
B1
Disable zone
Use the keypad to type the zone number (01-99). Press "A".
If "Automatically re-enablement" shall be used. Press “1”, insert time
(hh:mm). Press “A”.
B2
Disable zone-address
Use the keypad to type the zone number (01-99) and address (01-
99). Press "A".
If "Automatically re-enablement" shall be used. Press “1”, insert time
(hh:mm). Press “A”.
B3
Disable output
Use the keypad to select type of output:
- 0 = Loop unit output.
- 1 = C.i.e. output S0 or S1.
- 2 = C.i.e. output R0.
- 3 = C.i.e. expansion board output.
Press "A".
Depending on the selected type, use the keypad to type additional
data:
- 0: Output number (0-2) and COM loop (technical) address.
- 1: Output (S) number 0-1.
- 2: Output (R) number 0.
- 3: Output number (0-7) and expansion board number (0-3).
Press "A".
B4
Disable all control, ventilation,
exting or interlocking outputs
Use the keypad to select type of output:
- 0=Outputs type Control (not control neutral).
- 1=Outputs type Ventilation.
- 2=Outputs type Extinguishing.
- 3=Output type Interlocking.
Press "A".
B5
Re-enable zone
Select a zone.
To re-enable the selected zone press "A".