14
DAILY USER´S MANUAL EBL128 VERSION 2.2.X DOCUMENT NUMBER: MEW01786 REVISION: 1
10. FAULT ACKNOWLEDGE (H6)
LED "Fault tx activated" on the front is indicating that the output for Fault condition routing equipment is
activated. The LED will be turned off when all faults are acknowledged.
LED "General fault" on the front is indicating that not all faults are acknowledged and corrected.
No status info. = not corrected / serviced and not acknowledged fault.
Acknowledged = not corrected / serviced but acknowledged fault.
Serviced = corrected / serviced but not acknowledged fault.
a) Log on to the c.i.e.
b) Navigate to menu H6.
c) Press "A". A list will be displayed, in which you can scroll. The most recent fault is on top of the list.
d) Scroll with and or press for more information.
e) To acknowledge the fault shown in the display, press the button "Fault acknowledge".
NOTE! A fault that is both serviced and acknowledged will disappear from the list.